Danfoss AK-SM 800A Series CISA KEV Flaws: RCE, Path Traversal and Auth Bypass, Upgrade Now

Cover card: Danfoss AK-SM 800A Series, three CISA KEV flaws (CVE-2023-25915, CVE-2023-25914, CVE-2025-41450), actively exploited, upgrade now.

Status: On November 25, 2026 (2:48 p.m. EST), CISA added three vulnerabilities in Danfoss AK-SM 800A Series refrigeration and commercial facility controllers to its Known Exploited Vulnerabilities (KEV) catalog. Two stem from DSA-2023-08-01 (August 21, 2023): CVE-2023-25915 (remote command execution) and CVE-2023-25914 (XML interface path traversal), both fixed in version 3.3, marked forensicTriage: Yes, and carrying a federal due date of November 28, 2026. The third, CVE-2025-41450 from DSA-2025-03-01 (March 24, 2025) and CISA ICS Advisory ICSA-25-140-03, is an authentication bypass exposing internal IP addresses, usernames and store names via a generated web report; it is fixed in version 4.2 (R4.2) and due December 9, 2026. Known ransomware campaign use is Unknown for all three.

CVE-2023-25915 is in CISA's Known Exploited Vulnerabilities (KEV) catalog, added November 25, 2026.

CVE-2023-25914 is in CISA's Known Exploited Vulnerabilities (KEV) catalog, added November 25, 2026.

CVE-2025-41450 is in CISA's Known Exploited Vulnerabilities (KEV) catalog, added November 25, 2026.

Executive Summary

Danfoss AK-SM 800A Series system managers provide system control and monitoring for Danfoss ADAP-KOOL refrigeration systems in food retail stores. Although Danfoss released fixes for the 2023 flaws in version 3.3 and for the 2025 authentication bypass in version 4.2, CISA's KEV addition signals active exploitation risk against unpatched units, with a three-day federal deadline (November 28, 2026) for the 2023 flaws.

CVE Advisory Weakness Affected Fixed KEV Due Date Forensic Triage
CVE-2023-25915 DSA-2023-08-01 Remote command execution (CWE-20) Below 3.3 3.3 Nov 28, 2026 Yes
CVE-2023-25914 DSA-2023-08-01 XML path traversal (CWE-22) Below 3.3 3.3 Nov 28, 2026 Yes
CVE-2025-41450 DSA-2025-03-01 / ICSA-25-140-03 Improper authentication (CWE-305 / CWE-287) Prior to 4.2 (R4.2) 4.2 (R4.2) Dec 9, 2026 No

What to do first:

  • Upgrade every AK-SM 800A Series controller below 4.2 to the latest supported firmware (at least 4.2 / R4.2 to resolve all three KEV flaws, and 4.3.1 or later to cover follow-on flaws in ICSA-25-140-03) (Rescana guidance).
  • Remove any direct internet exposure immediately and place controllers behind firewalls and VPNs, following Danfoss and CISA guidance.
  • Perform forensic triage on exposed controllers below 3.3, because CISA flags both 2023 CVEs for forensic triage and patching does not remove prior unauthorized access (Rescana guidance).

Technical Information

This section relies solely on Danfoss advisories (DSA-2023-08-01, DSA-2025-03-01), Danfoss's AK-SM 800A downloads page, CISA ICS advisories (ICSA-25-140-03, ICSA-26-328-03), CISA's KEV catalog, NVD and CVE.org records. A public proof-of-concept (PoC) reference exists for CVE-2025-41450 (NVD lists one); we did not open, link or describe that PoC. On CVE.org (updated November 25, 2026, 3:17 p.m. EST), CISA's ADP container records SSVC Exploitation as active for all three CVEs (with Automatable: no and Technical Impact: total for CVE-2023-25915 and CVE-2023-25914, and Automatable: no and Technical Impact: partial for CVE-2025-41450).

CVE-2023-25915, Remote Command Execution (CWE-20). Danfoss DSA-2023-08-01 states that due to improper input validation, a remote attacker could execute arbitrary commands on the target system. DIVD's CNA record and NVD specify that an authenticated remote attacker could execute arbitrary commands (PR:L). NVD's primary assessment scores CVE-2023-25915 at CVSS 3.1 8.8 (High) (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H, scope unchanged). Danfoss DSA-2023-08-01 lists a 9.8 base score, and DIVD's CNA record lists 9.9 (AV:N/AC:L/PR:L/UI:N/S:C/C:H/I:H/A:H, scope changed).

CVE-2023-25914, XML Interface Path Traversal (CWE-22). DIVD's CNA record and NVD state that due to improper restriction, authenticated attackers could retrieve and read system files of the underlying server through the XML interface, which can lead to full system compromise. NVD and DIVD's CNA record both score CVE-2023-25914 at CVSS 3.1 8.8 (High) (AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H), while Danfoss DSA-2023-08-01 lists 7.5 (High).

CVE-2025-41450, Improper Authentication (CWE-305 / CWE-287). Danfoss DSA-2025-03-01 and CISA KEV report that an authentication flaw lets an attacker generate a web report disclosing sensitive information including internal IP addresses, usernames and store names. CISA ICSA-25-140-03 notes unauthorized access stems from datetime-based password generation prior to R4.2. NVD analyzed CVE-2025-41450 on November 25, 2026 (3:24 p.m. EST), assigning a Primary score of CVSS 3.1 7.5 (High) (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N) alongside Danfoss as CNA at CVSS 3.1 8.2 (High) (AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:H). ICSA-25-140-03 also lists CVSS 4.0 7.3 (High). The current ICSA-25-140-03 text (last revised November 18, 2026) still states that no known public exploitation had been reported to CISA; CISA's November 25 KEV addition supersedes that statement.

Combined exposure risk (Rescana guidance). On controllers below 3.3, bypassing authentication (via CVE-2025-41450 or CVE-2023-25913, also fixed in 3.3) could enable authenticated PR:L file reads (CVE-2023-25914) and command execution (CVE-2023-25915). Units on 3.3 through 4.1.x remain exposed to CVE-2025-41450.

Affected Product Versions

  • Danfoss AK-SM 800A Series below 3.3: Affected by CVE-2023-25915, CVE-2023-25914 and CVE-2025-41450. Danfoss DSA-2023-08-01 states version 3.3 remediates the 2023 issues (CVE-2023-25914, CVE-2023-25915 and CVE-2023-25913). NVD CPE entries list versionEndIncluding: 3.3, whereas Danfoss and DIVD specify versions below 3.3 are affected and 3.3 is fixed.
  • Danfoss AK-SM 800A / 8xxA Series prior to 4.2 (R4.2): Affected by CVE-2025-41450; fixed in 4.2 (R4.2) per DSA-2025-03-01 and ICSA-25-140-03, and NVD's CPE entry specifies ak-sm_800a_firmware below 4.2 (versionEndExcluding: 4.2). Upgrading to 4.2 or later resolves all three KEV flaws and clears any <= 3.3 CPE ambiguity (Rescana guidance).
  • Broader AK-SM 8xxA baseline and Strict Mode: ICSA-25-140-03 (Update A) fixes two post-authenticated flaws in 4.3.1, and ICSA-26-328-03 (November 24, 2026) warns of an unauthenticated CGI buffer overflow in AK-SM8xxA <= 5.4.0 (fix planned for 5.5.x). Danfoss's downloads page notes that 4.0.x and above enable Strict Session Control (Strict mode) by default on reboot, enforcing HTTPS, session-token authentication for XML and Northbound XML string sanitization. Because upgrading an HTTP-configured unit or third-party XML 1.0 integration can disrupt remote sessions, Danfoss strongly recommends on-site updates (or on-site staff) when web or XML settings are uncertain, and requires version 5.0 or above (and recommends 5.1 or above) before installing the latest EDF device-file packages.

How to Find Your Exposure

  • Inventory every Danfoss AK-SM 800A / 8xxA controller across stores, cold storage and labs, recording exact firmware versions and whether HTTP or Strict Mode is active (Rescana guidance).
  • Check internet and remote-access exposure immediately for controllers assigned public IP addresses or reachable without a VPN (Rescana guidance).
  • Verify firmware levels with refrigeration and BMS contractors who remotely manage store controllers (Rescana guidance).

Workaround and Mitigation

Danfoss lists "N/A" under Mitigations in both DSA-2023-08-01 and DSA-2025-03-01, directing operators to upgrade via the Danfoss AK-SM 800A Series download page. CISA's KEV required action mandates compliance with BOD 26-04 and Forensics Triage Requirements, evaluating internet exposure, or discontinuing use if mitigations are unavailable.

Per ICSA-25-140-03, ICSA-26-328-03 and Danfoss's downloads page:

  • Do not expose devices directly to the internet or assign public IP addresses; isolate control networks behind firewalls separate from business networks.
  • Require secure VPNs for all remote administration and vendor access.
  • Keep Strict Mode enabled on 4.0.x and above rather than reverting to Backward Compatible HTTP mode.
  • Use strong, unique passwords for all user and administrative accounts.

Post-patch steps (Rescana guidance):

  • Perform forensic triage on exposed units below 3.3: inspect controller logs, web/XML access records, local accounts and configuration backups for unauthorized access before patching.
  • Rotate controller and connected credentials after upgrading, particularly if any unit below 4.2 was reachable from untrusted networks.

Indicators of Compromise

Danfoss and CISA have not published indicators of compromise (IoCs) for CVE-2023-25915, CVE-2023-25914 or CVE-2025-41450. We do not list any. Monitor logs for unexpected XML requests, unauthorized web-report generation, unfamiliar local accounts or unexpected restarts, and watch Danfoss and CISA advisories for updates (Rescana guidance).

Timeline (EST)

  • August 21, 2023, 3:30 p.m. EST: DIVD publishes CVE-2023-25914 and CVE-2023-25915; Danfoss publishes DSA-2023-08-01 (fixed in 3.3). NVD publishes both records at 4:15 p.m. EST.
  • March 24, 2025: Danfoss publishes DSA-2025-03-01 for CVE-2025-41450 (fixed in 4.2).
  • May 8, 2025, 4:41 a.m. EST: Danfoss CNA publishes CVE-2025-41450; NVD publishes the record at 5:15 a.m. EST.
  • May 20, 2025: CISA publishes ICSA-25-140-03 (Update A August 26, 2025; revised November 18, 2026).
  • September 1, 2025: Danfoss updates DSA-2025-03-01 Problem Type to CWE-305.
  • November 24, 2026: CISA releases ICSA-26-328-03 (AK-SM 8xxA <= 5.4.0), emphasizing Strict Mode and network isolation.
  • November 25, 2026, 2:48 p.m. EST: CISA releases KEV catalogVersion 2026.11.25 (1,805 entries), adding CVE-2023-25915 and CVE-2023-25914 (due November 28, 2026, forensic triage Yes) and CVE-2025-41450 (due December 9, 2026, forensic triage No).
  • November 25, 2026, 3:17 p.m. EST: CISA ADP updates CVE.org records for CVE-2023-25914, CVE-2023-25915 and CVE-2025-41450 with KEV catalog references and SSVC Exploitation: active.
  • November 25, 2026, 3:24 p.m. EST: NVD marks CVE-2025-41450 as Analyzed with Primary CVSS 3.1 7.5 (High) and CPE below 4.2.
  • November 25, 2026, 3:32 p.m. EST: Our HOLD re-pull and verification of Danfoss advisories, downloads page, CISA ICS advisories, KEV, CVE.org and NVD.

Third-Party Risk (TPRM) Angle

Food retail and cold-chain operators often rely on refrigeration contractors and BMS integrators who manage AK-SM 800A controllers across stores (Rescana guidance). An exposed unit or shared contractor VPN can leak store names, usernames and internal IPs (CVE-2025-41450) or allow command execution (CVE-2023-25915).

Questions for refrigeration and BMS providers (Rescana guidance):

  • Do you operate or remotely maintain Danfoss AK-SM 800A / 8xxA Series controllers at any of our sites or over a shared management network?
  • What firmware version runs on each controller, and when will units below 3.3 or 4.2 be upgraded?
  • Are any units internet-reachable, assigned public IPs, or operated without VPN access and Strict Mode?
  • For any exposed unit below 3.3, have forensic triage and credential rotation been completed?

Need help identifying exposed OT/ICS controllers across your locations and third-party maintenance partners? Talk to an expert

Sources

Talk to an expert

Talk to Rescana about this advisory — or about how we help TPRM teams keep reviews moving.